给水排水设计规范2016 (给排水设计规范施行)
《修建给水排水规划标准》重要设备机房不允许有水...
《修建给排水规划标准》GB50015标准相关条款摘录供参阅:
3.5.7 室内给水管道不该穿越变配电房、电梯机房、通信机房、大中型计算机房、计算机网络中
心、音像库房等遇水会损坏设备和引发事端的房间,并应防止在出产设备、配电柜上方经过。
3.5.10 给水管道不得敷设在烟道、风道、电梯井内、排水沟内。给水管道不宜穿越橱窗、壁柜。
3.5.20 给水管道应防止穿越人防地下室,有必要穿越时应按现行国家标准《公民防空地下室规划标准》GB 50038的要求设置防护阀门等办法。
4. 3. 3 修建物内排水管道安置应契合下列要求:
3 排水管道不得敷设在对出产工艺或卫生有特殊要求的出产厂房内,以及食物和宝贵产品库房、通风小室、电气机房和电梯机房内;
4 排水管道不得穿过沉降缝、伸缩缝、变形缝、烟道和风道;当排水管道有必要穿过沉降缝、伸缩缝和变形缝时,应采纳相应技术办法;
5 排水埋地管道,不得安置在或许受重物压害处或穿越出产设备根底;
6 排水管道不得穿越住所客厅、餐厅,并不宜接近与卧室相邻的内墙;
7 排水管道不宜穿越橱窗、壁柜;
修建给水排水规划标准的目录
1GeneralPrinciples
2TermsandSymbols
2.1Terms
2.2Symbols
3WaterSupply
3.1Ratedwaterconsumptionandwaterpressure
3.2Waterqualityandwaterqualitypollutionprotection
3.3Systemselection
3.4Pipematerial,fittingsandwatermeter
3.5Pipinglayoutandpipelaying
3.6Designflowandhydrauliccalculationofpipe
3.7Watertower,Watertank,Reservoir
3.8Pressurizingequipment,pumphouse
3.9Swimmingpoolandaquaticrecreationpool
3.10Coolingtowerandcirculationcoolingwater
3.11Waterscape
4WaterDrainage
4.1Selectionofdrainagesystem
4.2Plumbingfixtureandwaterlock
4.3Pipelocationandpipelining
4.4Calculationofdrainagepipe
4.5Pipematerial,fittingsandinspectionwell
4.6Ventpipe
4.7Sewagepumpandcatchpit
4.8Smalldomesticsoildisposal
4.9Rainwater
5Hotwateranddrinkingwatersupply
5.1Ratedconsumption,temperatureandqualityofhotwater
5.2Selectionofhotwatersupplysystem
5.3Calculationofheatconsumption,hotwaterquantityandheatingequipmenthotsupply
5.4Waterheatingandstorage
5.5Calculationofnetwork
5.6Pipe,fittingandpipelinelaying
5.7Potablewatersupply
AppendixAResidentialdistrictundergroundpipeline(structure)minimumnetclearancebetweenlines
AppendixBValvesandscrewfittingsresistancelossconvertedlengthofcompensation
AppendixCWatersupplypipesectionPlumbingfixtureswatersupplyequivalentsimultaneouslyoutflowprobabilitycalculatedequation,accoefficientvaluestable
AppendixDWatersupplypipesectiondesignedsecondflowcalculationtable
AppendixEFinedrinkingwaternumberoftapssimultaneouslyuseinthecalculatedpipesection
ExplanationofwordinginthisCode
第四条说的轴线应该是墙的轴线,便是说规划的时分不论管线怎么走都要和结构图里的墙轴线平行,留意,是和一切的轴线都平行或许笔直,比方对面墙的轴线,便是说断面和平面都平行。遇到梁、柱之类的妨碍应挑选90度的转角这样能够确保平行。第五条、其实说的便是重力流水高问题,你应该知道管径不同的接头时应该确保流水高一平,所以应该把支管规划在干管上面,最好不要过管中(这个说的是干管处于水平状态下)